High-Voltage Fuse for Overload Protection of Oil-Immersed Transformer

  • Model NO.: PRNT-15.5/-1.8
  • Type: Current Fuse
  • Shape: Insert
  • Fusing Device: Link Break
  • Trademark: zhenli
  • Origin: Xi′an
  • Breaking Capacity: High
  • Usage: High Voltage
  • Fusing Speed: FF
  • Standard: UL
  • Transport Package: Carbon
  • HS Code: 8535100000

High-voltage fuse for overload protection of oil-immersed transformer

This product applies to indoor AC 50~60Hz system with the rated voltage of 15.5kV and shall be used in series with the backup fuse for oil-immersed transformer overload protection, and can provide the full range protection for indoor power system. The product has passed the type test conducted by the national high-voltage electrical equipment quality supervision and inspection center, and conforms to GB15166.2 and IEC282-2.
Model:
 High-Voltage Fuse for Overload Protection of Oil-Immersed Transformer

Basic parameters:
 
Product Model Rated Voltage
 (kV)
Maximum Voltage
 (kV)
Rated Current
 (A)
Rated Maximum Breaking Current (kA) Application Conditions
PRNT-15.5 15.5 17.2 6,10,16,25,40,50,
60,100,140
1.8 Transformer oil
Outline and installing dimensions:
 High-Voltage Fuse for Overload Protection of Oil-Immersed TransformerHigh-Voltage Fuse for Overload Protection of Oil-Immersed Transformer


                                           Fig.2 Dimensions of the Overall and Installation
Main technical performance:
 High-Voltage Fuse for Overload Protection of Oil-Immersed Transformer          
Fig.3 the fuse and backup fuse protection feature
Note: Point A: the intersection of two curves
Point B: rated minimum breaking current of backup fuse
Point C: rated maximum breaking current of fuse
During the operation, point A must be present and point B is above point A
Point C is below point A.
 High-Voltage Fuse for Overload Protection of Oil-Immersed Transformer

  Fig. 4 Time - current characteristic curve
 
 
 
 
Installation and use
1. When mounting the fuse into the tank, ensure the oil level is within the range as shown in Fig. 2
2. When replacing the fuse, open the buckle on the handle and turn the handle for 90° to eliminate the adhesion between the sealing gasket and outer tube. Remove and replace the handle.
3. For the installation of three-phase fuse, replace all three phases unless you can confirm that the fault current passes through one phase.
 

The offered LED Mini Spot Light is highly demanded in our clients in order to augment the beautification of the place. Our spot light is extensively demanded in the market for its stylish design, long lasting finish, amazing look, high brightness and energy efficiency. This beautiful spot light is manufactured using latest technological advancements and quality assured raw materials in a variety of sizes and other related specifications.

We use aluminum and die-casting as the lamp body performing great in heat dissipation to expand the lifespan. This beautiful spot light is manufactured using latest technological advancements and quality assured raw materials in a variety of sizes and other related specifications. We offer 4W and 6w spotlight, in E27, GU5.3, GU10 and MR16 lamp base for our clients

LED Spotlight

LED Spotlight, 12V LED Spotlight, High Power LED Spotlight, Gu10 LED Spotlight

Dearhe Optoelectronics Techco.Factory in Shenzhen,China , http://www.dearheledfactory.com